beautypg.com

Installation instructions, Adjustment and testing, Maintenance and troubleshooting – Powers ES150 Emergency Tempering Valves with Internal Cold Water Bypass User Manual

Page 2: Operation

background image

What to look for if:
• The flow of water is less then desired.

a. Stop valves or supply to HydroGuard

®

not fully open.

b. Clogged checkstop strainer screens.

c. Accumulation of lime deposit around valve seats.

d. Low supply pressure or unusual supply temperature.

The flow of water is completely shut off.

a. Stop valves or supply valves are completely closed.

b. Valves downstream from HydroGuard® fully closed.

c. Loss of cold water supply pressure

1. Flush all piping thoroughly before installing.

2. The installation and field adjustment of ES150 is the respon-

sibility of the installer and shall be carried out in accordance

with the following steps.

3. Locate ES150 as close as possible to the fixture being sup-

plied. It shall be accessible for testing, adjustment and/or

maintenance in its installed position.

4. Shutoff valves are installed for maintenance purposes.

Provision shall be made to prevent unauthorized shutoff.

5. When ES150 supplies tempered water to self-closing and/or

solenoid valves, provide a shock absorber (Powers' part # 460

353) on the discharge line. This protects the ES150 actuator

from damage by water shock waves generated by quick clos-

ing valves.

6. Consult proper medical/safety authorities for the

optimum temperature for your application. Before

use, check for proper discharge temperature. Reset

if necessary. Valve is preset for 85°F (29°C)

1. Loosen adjustment locking screw

2. Check outlet temperature, which is factory set to 85°F (29°C).

If it is not, reset it by rotating temperature adjustment screw

clockwise to reduce temperature or counterclockwise to

increase the outlet temperature.

3. Close cold water checkstop. Verify that flow shuts down

immediately.

4. Open cold water checkstop. Close hot water checkstop.

Verify adequate flow from fixture(s).

5. Open hot water checkstop, verify temperature returns to set

temperature.

6. Tighten adjustment locking screw.

7. Record test data on maintenance tag which should be pro-

vided by the facility.

NOTE:

Contact Powers application department at

800.669.5430 for high temperature readjustment pro-

cedure.

Installation Instructions

n

Adjustment and Testing

n

Maintenance and Troubleshooting

n

2

Hot and cold water supplies enter HydroGuard

®

XP at indicated

ports (see Fig. 1) then flow past plunger and seats. Next, hot

and cold water flow is directed to the mixing chamber where the

thermostatic actuator is located.

The temperature adjustment screw moves the actuator to

determine the discharge temperature. If discharge temperature

rises due to inlet pressure or temperature, the actuator expands,

decreasing flow of hot water. The reverse occurs with a drop in

discharge temperature.

Cold water supply failure - causes actuator to expand effectively

closing hot water port.

Hot water supply failure - causes actuator to contract opening

cold water bypass ports.

Body

Cold Water

Mixing Chamber

Secondary Bypass Spring

Primary Bypass

Secondary Bypass

Temperature

Adjustment

Screw

Adjustment

Locking

Screw

Thermostatic

Actuator

Hot Water

Hot/Cold Water Shuttle

Return Spring/

Primary Bypass Spring

Figure 1

Operation

n