Powers ES150 Emergency Tempering Valves with Internal Cold Water Bypass User Manual

Technical instructions, Description, Specifications

background image

ES150 HydroGuard

®

XP Emergency Tempering valves thermostatically blend

hot and cold water to deliver tepid water to emergency fixtures, quickly com-

pensating for temperature variations due to the changes in inlet temperature

or pressure. Powers' exclusive internal bypass ensures cold water flow in

the event of loss of hot water.
US Patent 6,575,377

Description

n

Connections ............................................................. 1/2" NPT inlets and outlet

Maximum Operating Pressure ............................. 125psi (861 kPa)

Maximum Hot Water Temperature . ..................... 180°F (82°C)

Temperature Adjustment Ranges ........................ 60 - 95°F (15 - 35°C)

Factory Set Temperature* .................................... 85°F (29°C)

Bypass Flow Rate at 30psid* ................................ 6.5 gpm (25 lpm)

Maximum Flow with Cold Water Shutoff* .......... 0.5 gpm (1.9 lpm)

Listing ........................................................................ ASSE 1071

* When tested under conditions specified in ASSE 1071 Standard

Specifications

n

HYDROGUARD

®

XP

Emergency Tempering Valve

with Cold Water Bypass

Technical Instructions

Capacity

n

Flow Capacity at 85°F (29.4°C)

P r e s s u r e D r o p A c r o s s V a l v e

Model

Min. Flow

C

V

5psi

10psi

15psi

20psi

30psi

45psi

60psi

to ASSE 1071

(34 kPa)

(69 kPa)

(103 kPa)

(138 kPa)

(207 kPa)

(310 kPa)

(414 kPa)

ES150

1.0 gpm

1.59

3.6 gpm

5.0 gpm

6.2 gpm

7.1 gpm

8.7 gpm

10.7 gpm

12.3 gpm

3.8 lpm

13.6 lpm

18.9 lpm

23.5 lpm

26.9 lpm

32.9 lpm

40.5 lpm

46.6 lpm

IS-P-ES150

Advanced Thermal Activation

WARNING

!

FAILURE TO COMPLY WITH PROPER

INSTALLATION AND MAINTENANCE

INSTRUCTIONS COULD CONTRIBUTE TO THE

VALVE FAILURE, RESULTING IN INJURY AND DEATH.

TO ENSURE THE ACCURATE AND RELIABLE
OPERATION OF THIS PRODUCT, IT IS ESSENTIAL TO:

• Properly size each valve based on the individual

application.

• Properly design the recirculation system to minimize

pressure and temperature variations.

• Check outlet temperature to ensure it does not

exceed 110°F (43°C). Make sure temperature limit

stop is properly reset to maximum 110°F (43°C)

following valve maintenance or repair. Tampering

with limit stop in any way may result in scalding

temperature causing serious bodily harm and/or

death.

Periodic Inspection/Maintenance: OPERATION

OF EMERGENCY VALVES AND FIXTURES SHOULD

BE TESTED WEEKLY PER ANSI Z358.1. In addition

conduct an annual maintenance program by a

licensed plumber or a qualified service techni-

cian to ensure proper operation of the critical

components. Regular checking and cleaning of the

thermostat assembly assures proper product func-

tion. Corrosive water conditions, temperatures over

210°F, unauthorized adjustments or repair could

render the valve ineffective for the service intended.