beautypg.com

Reverse acting (cooling application), Specifi cations, Applications – Powers 595 Series 11 Self-Operating Temperature Regulators - Type ST Stainless Trim User Manual

Page 2: 3 cm

background image

2

Reverse Acting (cooling application)

(C) When the temperature of the process fl uid rises toward or
above the set point, the temperature of the thermally responsive
fl uid increases, which increases vapor pressure in the bulb/
bellows. The resulting force of the vapor pressure is greater
than the spring force, so the spring contracts and the bellows
expand to push the valve plug downward, away from its seat.
This increases the fl ow of the cooling medium, which lowers the
temperature of the process fl uid.

(D) As the process fl uid temperature decreases toward or below
the desired set point, the temperature of the thermally respon-
sive fl uid decreases, causing the vapor pressure to decrease.
This contracts the bellows and expands the spring to pull the
valve plug up towards its seat, to reduce or stop the fl ow of the
cooling medium.

Specifi cations

Physical
Valve Sizes: ....................................... 1/2"A, 1/2"B, 1/2"C,

1/2"D, 1/2", 3/4", 1" (NPT)

Body Material: ................................. Bronze
Body Rating: ...................................... ANSI Class 250
Connections: ..................................... Double Female Unions with

Pipe Thread

Style: ................................................... Single Seat, Stainless Steel

Trim, V-Port

Valve Plug Travel: ........................... See Dimensional Data

on page 10

Effective Bellows Area: ................. 7.8 in

2

(50.3 cm

2

)

Maximum Body Temperature: ..... 400°F (204°C)

Operating Temperature
Range
: ................................................ See Order Code on page 15
Controlled Medium: ........................ Steam, water and fl uid not

corrosive to stainless steel
and bronze

Maximum Differential Pressure: See Tables on pages 3 & 4
Maximum Allowable
Overheat Temperature:
.................. 25°F (14°C) above range
Maximum Well Safe Pressures: . See Table on page 10
Maximum Body Pressure: ............. 250 psi (1723.75 kPa)
Shipping Weight: ............................. See Table 11
Flow Characteristics: ..................... Modifi ed Parabolic
Shutoff Class Rating: ...................... ANSI Class III (Leakage

0.1% of rated valve capacity)

Applications

Powers #11 Regulators are used to automatically control the
temperature of a fl uid, specifi cally in processes requiring high
pressure steam (up to 200 psi). The self-actuated Regulator can
easily be installed in any convenient location. Among its applica-
tions are: hot water systems, fuel oil heaters, control for jacket
water cooling for air compressors, dairy equipment, and many
industrial processes. Below are two typical applications.

#11 Regulator ST

Single Seat

DIRECT ACTING

#11 Regulator WM

Water Mix

Bulb in Well

Bulb in Well

Steam

Supply

Pump

Pump

Check

Valves

Cold Water Supply

HTHW Return

WATER HEATER

Tempered

Return

HTHW

Tempered

Water

To Condensate Return

Quench Tank Application

Jacket Water Cooling Application

#11 Regulator

Single Seat ST

REVERSE ACTING

Surge Tank

Engine

or

Compressor

Circulating

Pump

Cold Water

Inlet

Overflow

Bulb in Well