System Maintenance

n

Routinely (twice a year) perform the following maintenance to

ensure safe continuous operation of ESP Hydropanel™ units.
1. Inspect electrical connections for corrosion.
2. Check for any loose connections. Tighten if necessary.
3. Check solenoid valve for proper operation. Make sure it is

free of dirt and lime build up.

4. Check that temperature of supply water is thermostatically

controlled for safe comfortable bathing.

For brass solenoid: For maintenance instructions, use Powers

Kit #444 183 and refer to “Installation and Maintenance

Instructions,” Series 8210, included with the ESP Hydropanel™

II Kit.

Parts List

n

No.

Part #

Description

1

444 416

Sensor Assembly for Pushbutton Shower

1A

444 416

Pushbutton Assembly

2

444 175

Solenoid Assembly (non-metallic)

3

444 175

Solenoid Assembly (brass)

4

444 161

Control Box, Individual Pushbutton Showers

5

444 118

Plug In Transformer

6

444 119

Box Transformer

No.

Part #

Description

7

141 379

Swivel Showerhead

8

141 816

Fixed Showerhead

Not Shown

444 168

Installation Kit, Pusbutton Control Box

Not Shown

444145C

Maintenance/Repair Kit, Solenoid (non-metallic)

Not Shown

444145D

Diaphragm Repair Kit, Solenoid (non-metallic)

Not Shown

444 183

Maintenance/Repair Kit, Solenoid (brass)

Solenoid Valve Maintenance

n

Maintenance and Troubleshooting

n

6

5

4

3

7

8

1 1a

2

The following are problems that may occur with the ESP

Hydropanel™ II. Follow the listed steps toward a solution. For

any further problems, call Powers Application Engineering

Deptartment at 1.800.669.5430.
Shower Control:
1. Iftheshowerdoesnotactivatewhenthepushbutton

ispressed:

a. Check that transformer feed wires are securely

attached to terminals at control box and at transformer.

b. Check that power is supplied to the transformer. Also,

use a voltmeter to check that power is being supplied

through the transformer. If power goes into the trans-

former but does not come out, replace the transformer.

2. Ifnowaterflowsfromshowerheadwhenpushbutton

ispressed:

a. Check that the supply line is open and water is being

supplied.

b. Check that the solenoid wires are securely connected.
c. The maximum run-time may have elapsed. Wait 5

seconds for sensor delay, then press the pushbutton

again. For a longer shower-run time, reset potentio-

meter on control box.

3. Ifwaterrunscontinuously,regardlessofsensoractivity:

a. FIRST unplug solenoid from the control box.
b. If water continues to run...

• Debris and/or lime build-up may be preventing

solenoid from closing. Dismantle, clean and flush the

solenoid valve (see Solenoid Valve Maintenance).

c. If water stops after disconnecting power...

• The problem is electronic. Check that power wires

are connected properly in the Control Box, and check

all electrical connections.