6.4 Table IIC

Level II Program Values - 962 Twin Tank Alternating Softener (P17=2)

Parameter

Description of

Program Values

Range of Values

Min.

Increment

Factory

Value

Units of Measure

Notes

P1

Day of Week and

Time of day

(1-7) 1:00 - 12:59

AM or PM

Metric

(1-7) 0:00 - 23:59

(1 day)

1 minute

None

Hour

Minute

Range depends on value selected for
P13. For day of week SUN=1, MON=2,
TUE=3, WED=4, THU=5, FRI=6, SAT=7.
THIS IS THE LEFT MOST DIGIT ON
THE DISPLAY.

P2

Time of day to start

regeneration

1:00 - 12:59 AM or PM

00:00 - 23:59

1

None

Hour

Minute

Range depends on value selected for
P13. Use only if P15 =1

P3

Hardness of water

3-250

30-2500

1

10

0

0

Grains per gallon

ppm

Unit of measure depends on value
selected for P12

P4

Salt amount

5 – 1250

2 - 500

5

2

10

4

Pounds

Kilograms

Unit of measure and factory value
depend on value selected for P12

P5

Capacity of unit

1-2600

0.1-260.0

1

0.1

0

Kilograins

Kilograms

Total capacity for each tank. Unit of
measure depends on value selected for
P12

P6

Refill controller

2 - 99

1

0

Selected from chart in

Performance Data Sections,

page 57

P7

Brine draw rate

2 - 99

1

0

Selected from chart in

Performance Data Sections,

page 58

P9

Backwash time

4 - 30

1

14

Minutes

P10

Rinse time

7 - 125

1

40

Minutes

P11

Purge time

2 - 19

1

4

Minutes

P12

Units of measure

0 - 1

1

0

0 = US, 1 = Metric

P13

Clock mode

0 - 1

1

0

0 = 12 hour clock, 1 = 24 hour clock

P14

Calendar override

0 - 30

1

0

Days

0 = no calendar override

P15

Regeneration

delay

0 - 1

1

0

0 = Immediate regeneration

1 = Regeneration delayed until time pro-
grammed in P2 is reached

P16

Capacity that must
be left on 2nd tank

to permit delayed

regeneration of 1st

tank

0 - 70

1

30

Percent of Total

capacity

Used only if P15 is set to 1

P17

Operation type

0 - 2

1

2

2 = Twin Alternating

P18

Salt/Capacity

Change Lock Out

0 - 1

1

0

0 = none 1 = Salt /Capacity Change
Locked Out

P19

Flow Sensor select

0

0 = Magnum IT NHWB, 1 = 1.0" Autotrol
Turbine, 2 = 2.0” Autotrol Turbine, 3 =
User defined
K-factor, 4 = User defined pulse
equivalent, 5 = Magnum IT HWB

P20

K-factor or Pulse

equivalent

0.01 -255.00

.01

0.01

Number used for Meter K-factor or Pulse
equivalent

P21

Remote

Regeneration

Switch Delay

1 - 254

1

60

Seconds

Time remote switch must be active to
start a regeneration.

P22

Factory Use Only

DO NOT

CHANGE

99

Do not change