6.3 Table IIB
Level II Program Values - 962F Single Tank Filter (P17=4)
Parameter
Description of
Parameter
Range of Values
Min.
Increment Factory Value Units of Measure
Notes
P1
Day of Week and
Time of day
1:00 - 12:59
AM or PM
0:00 - 23:59
1
None
Day
Hour:Minute
Range depends on value selected for
P13. For day of week SUN=1, MON=2,
TUE=3, WED=4, THU=5, FRI=6,
SAT=7. This is the left most digit on the
display.
P2
Time of day to start
regeneration
1:00 - 12:59 AM or PM
00:00 - 23:59
1
2:00 AM
Hour:Minute
Range depends on value selected for
P13. Use only if P15 =1
P3
Factory
10
100
Grains per gallon
ppm
Unit of measure depends on value
selected for P12
P4
Salt amount
0.5 – 125.0
0.2 - 50.0
0.5
0.2
0.5
0.2
Pounds
Kilograms
Unit of measure and factory value
depend on value selected for P12
P5
0
U.S. - Divide the volumetric capacity
(gallons) of the filter by 100 and enter
this number into P5.
Metric - Divide the volumetric capacity
(cubic meters) by 10 and enter this
number into P5.
P6
Refill controller
2 - 200
1
200
gpm x 100
Do not change.
P7
Brine draw rate
2 - 200
1
200
gpm x 100
Do not change.
P9
Backwash time
7 - 60
1
14
Minutes
May be adjusted for application.
P10
Does not apply
7 - 125
1
8
Minutes
Do not change
P11
Purge time
9 - 60
1
9
Minutes
May be adjusted for application.
P12
Units of measure
0 - 1
1
0
0 = US, 1 = Metric
P13
Clock mode
0 - 1
1
0
0 = 12 hour clock, 1 = 24 hour clock
P14
Calendar override
0 - 30
1
0
Days
0 = no calendar override
P15
Reserve Type
0 - 3
1
0
0 = variable reserve 1 = fixed reserve,
2 = variable reserve with immediate
regen, 3 = fixed reserve with immediate
regen.
P16
Initial average
usage or fixed
reserve
0 - 70
1
30
Percent of Total
capacity
Description depends on value entered
for P15.
P17
Operation type
0 - 7
4
0
4 = filter
P18
Salt/Capacity
Change Lock Out
0 - 1
1
0
0 = none 1 = Salt /Capacity Change
Locked Out
P19
Flow Sensor select
1 - 4
1
0
0 = Magnum IT NHWB
1 = 1.0" Autotrol Turbine
2 = 2.0” Autotrol Turbine
3 = User defined K-factor
4 = User defined pulse equivalent
5 = Magnum IT HWB
P20
K-factor or Pulse
equivalent
0.01 -255.00
0.01
0.01
Number used for Meter K-factor or
Pulse equivalent
P21
Remote
Regeneration
Switch Delay
1 - 254
1
60
Seconds
Time remote switch must be active to
start a regeneration.
P22
Factory Use Only
0 - 9
1
99
Do not change.