3 applying power to the gateway or node, 4 bind radios to form networks – Banner SureCross DX80 Wireless Networks User Manual
Page 15

3.3 Applying Power to the Gateway or Node
Wire Color
Gateway (10–30V
dc)
Node (10–30V dc)
Node (FlexPower)
1
2
3
4
5
1
brown
10–30V dc input
10–30V dc
2
white
RS485 / D1 / B / +
3
blue
dc common (GND)
dc common (GND)
dc common (GND)
4
black
RS485 / D0 / A / -
5
gray
Comms gnd
3.6–5.5V dc*
* Do not apply more than 5.5V dc to the gray wire.
1. Apply power to the Gateway by connecting the 10–30V dc cable as shown.
The Gateway begins in RUN mode, displays the current network ID (NID), then identifies itself as a Gateway.
2. Apply power to the Node by connecting the 10–30V dc cable or the DX81 Battery Supply Module as shown. To apply
power to a FlexPower Node with an integrated battery, install the battery into the housing.
The Node starts in RUN mode, displays the current network ID, then identifies itself as a Node and lists its device ID.
3.4 Bind Radios to Form Networks
Binding Nodes to a Gateway ensures the Nodes only exchange data with the Gateway they are bound to. For a more
detailed definition of binding mode, refer to the Advanced Setup section of the SureCross Wireless I/O Networks
instruction manual.
Apply power to the Gateway and Nodes.
1. Enter binding mode on the Gateway.
•
If you have a two-button Gateway, triple-click button 2
•
If you have a one-button Gateway, triple-click the button
•
If you have a Gateway with no buttons, remove the rotary dial access cover and set both the right and left rotary
dials to 0, then set both the right and left rotary dials to F.
The red LEDs flash alternately when the Gateway is in binding mode. Any Node entering binding mode will bind to this
Gateway.
2. Enter binding mode on the Node.
•
If you have a two-button Node, triple-click button 2.
•
If you have a one-button Node, triple-click the button.
•
If you have a Node with no buttons, remove the top cover and set both the left and right rotary dials to F to enter
binding mode.
1
The Node enters binding mode and locates the Gateway in binding mode.
For two LED models, the red LEDs flash alternately. After binding is complete, both LEDs are both solid red for a few
seconds.
For one-LED models, the red and green LED flashes alternately while the Node searches for the Gateway. After binding
is complete, the LED is red and green for four seconds (looks orange), then the red and green flash simultaneously
(looks orange) four times.
The Node automatically exits binding mode, cycles its power, then enters RUN mode.
3. Use the Node's rotary dials to assign a valid decimal Node Address (between 01 and 47). The left rotary dial represents
the tens digit (0 through 4) and the right dial represents the ones digit (0 through 9) of the Node Address.
4. Repeat steps 2 and 3 for all Nodes that will communicate to this Gateway.
1
Some older M-GAGE Nodes (models DX80N*X1W0P0ZR) may require F-F binding despite having a single button.
SureCross Wireless I/O Networks
15