Embedded I/O Chapter 3
Local:4:O.CtrXZInvert
Use this tag to control the Z inputs of counter X when the ZInhibit tag for the same
counter is set.
A 0 value in this ZInvert tag causes the Z input value to be 0. A 1 value in this
ZInvert tag causes the Z input value to be 1.
Local:4:O.CtrXZInhibit
Use this tag to control the counter X Z input source.
A 0 value in this ZInhibit tag allows HSC input to control the Z input. A 1 value in
this ZInhibit tag allows the controller (that is, the value of the ZInvert tag) to control
the Z input.
Local:4:O.CtrResetRisingEdgeZ
Use this tag value to clear the latched rising edge of the Z input for counter X (that
is, the CtrXRisingEdgeZ tag value).
The value of this CTRResetRisingEdgeZ tag must transition from 0 to 1 in order to
clear the CtrXRisingEdgeZ tag value.
Local:4:O.CtrXResetCtrPresetWarning
Use this tag to clear the CtrXPresetWarning tag (located in the CtrXStatus array).
To clear the CtrXPresetWarning tag, this tag value must transition from 0 to 1.
Local:4:O.Range0To3
Range control tags. Use these tags to specify the behavior of the ranges when
using range output control of the counters.
(3)
Local:4:O.Range0To3[X]
Range control tags specific to range X.
Local:4:O.Range0To3[X].HiLimOrDirWr
When range X’s LoadDirectWrite tag is set to 0, this tag contains the range X High
Limit value used in the range comparison.
When the LoadDirectWrite tag (located within tag Range0To3[X].Config) transitions
from 0 to 1, this tag value is written to counter X's current count.
Local:4:O.Range0To3[X].LowLimit
When range X’s LoadDirectWrite tag is set to 0, this tag contains the range X Low
Limit value used in the range comparison.
When the LoadDirectWrite tag (located within tag Range0To3[X].Config) is set to 0
to 1, this tag value is not used.
Local:4:O.Range0To3[X].OutputControl
Use this tag to designate the HSC outputs (real and virtual) that are to be turned ON
when the range comparison results in range X are active.
Each output that has 1 specified in these tags is turned ON when the range X
comparison result is active.
(4)
Local:4:O.Range0To3[X].Config
Use the tags in this Config group to configure range X parameters.
Local:4:O.Range0To3[X].ToThisCounter_0
Use this tag value (along with the next tag - this is two-bit control field) to indicate
the counter to be used by range X in its range comparison.
HSC Tag Descriptions
Tag Name
Description