Using the Integral Keypad to Program and Control the Drive

8-5

8.4

Viewing and Adjusting Basic (P) and
Advanced (A) Parameters

Use the following procedure to view and adjust the Basic and
Advanced parameters.

To adjust additional parameters, repeat steps 2 through 7.

To exit a parameter without saving the value, press

instead of

.

Table 8.3 – Viewing and Adjusting Basic (P) and Advanced (A) Parameters

Procedure

Sample Display

Step 1.

Press

until the desired

parameter group is displayed.
The PROGRAM LED will turn
on to indicate the drive is in
program mode.

Step 2.

Press

to scroll

through the parameters in the
selected parameter group.

Step 3.

Press

to view the value

of the displayed parameter.

Step 4.

Press

or

.

The adjustable value will flash
on the display.

Step 5.

Use

to adjust the

value.

Step 6.

Press

to accept the

value. The value stops
flashing.

Step 7.

Press

to return to the

parameter number.