2 input power conditioning – Rockwell Automation MD60 User Manual Version 3.0 User Manual
Page 26
5-4
MD60 AC Drive User Manual
5.2.2 Input Power Conditioning
The drive is suitable for direct connection to input power within the
rated voltage of the drive (see table 5.4). Table 5.1 lists certain input
power conditions that may cause component damage or reduction
in product life. If any of the conditions exist, install one of the
devices listed in the ”Corrective Action” column in table 5.1 on the
line side of the drive.
Important:
Only one device per branch circuit is required. It
should be mounted closest to the branch and sized to
handle the total current of the branch circuit.
Table 5.1 – Corrective Actions for Input Power Conditions
Input Power Condition
Corrective Action
Low line impedance (less than 1% line
reactance)
•
Install line reactor
1
or
•
Install isolation
transformer
Greater than 120 kVA supply transformer
Line has power factor correction capacitors
Line has frequent power interruptions
Line has intermittent noise spikes in excess of
6000V (lightning)
Phase-to-ground voltage exceeds 125% of
normal line-to-line voltage
•
Remove MOV jumper to
ground and install
isolation transformer
with grounded
secondary, if necessary.
Ungrounded distribution system
1
Contact Reliance Electric for application and ordering information.