TL-Series Electric Cylinders 27

Rockwell Automation Publication TLAR-IN001B-EN-P - February 2014

9. Enter the Accel Limit, Decel Limit, and the User Units by using values from the

following table.

User Units can be entered in rev/mm or rev/in. Your choice determines the unit of
measure for the axis.

10. From the Drive Organizer, click Homing.
11. Enter values from the following table.

These values are recommended; your application can require different values.

12. Select the recommend homing method ID = 33, Home to marker, Reverse.

13. Click Start Homing.

Cat. No.

Accel/Decel Limits
rpm/s

User Units
rev/mm (rev/in.)

TLAR-x1xxxB-Bxx

120000

0.33333 (8.46667)

TLAR-x1xxxE-Bxx

36000

0.10000 (2.54000)

TLAR-x2xxxC-Bxx

72000

0.20000 (5.08000)

TLAR-x2xxxF-Bxx

28346

0.07874 (2.00000)

TLAR-x3xxxE-Bxx

36000

0.10000 (2.54000)

TLAR-x3xxxH-Bxx

18000

0.05000 (1.27000)

Parameter

Metric

English

Home Accel/Decel

10.0000 mm/s

2

0.3937 in/s

2

Home Offset

0.0000 mm

0.0000 in.

Home Velocity Fast

10.0000 mm/s

0.3937 in/s

Home Velocity Slow

10.0000 mm/s

0.3937 in/s

Home Switch

Input B1