Compliance with European Union Electromagnetic Compatibility Standards
B-5
B.3 Mounting the Equipment
Mount all electronic and electromagnetic components, including the drive and the
mains filter, firmly to the base mounting panel. The mounting panel must have good
conductivity, as described in section B.2.1, Selecting a Mounting Panel and Electrical
Cabinet.
These sections provide more detail on mounting the drive, AC mains filter, and AC
mains inductor.
B.3.1 Mounting the Drive
If the cabinet includes ventilation louvers or filter and fan openings in the sides or door,
the openings cannot be located within a zone 254 mm (10 inches) above and below
the height of the drive, as shown in figure B.1.
Figure B.1 – Prohibited Area for Cabinet Ventilation Openings
B.3.2 Mounting the AC Mains Filter
Refer to figures B.2 through B.5 for filter mounting dimensions. The filter can be
mounted either flat, with its back against the panel, or on its side, with either side
against the panel.
If the 3DF4359 is mounted on its side, it must be mounted on the L bracket first.
(included with the filter). Mount the L bracket using 12 mm screws. See figure B.6 for L
bracket filter mounting.
254 mm
(10 in)
FlexPak
3000
Drive
254 mm
(10 in)
No cabinet openings
in the doors or sides
are permitted in the
shaded area