Figure 5 - Fiber Cable

Specifications

The 1756-EN2F EtherNet/IP fiber module and the 1783-ETAP1F and
1783-ETAP2F EtherNet/IP fiber taps use a fiber cable and LC connector. The
fiber cable is typically used in 1 m (3 ft), 2 m, (6 ft), 3 m (9 ft), 5 m (15 ft), and
100 m (300 ft) lengths, but supports lengths up to 2 km (1.24 mi).

The fiber cable and LC connector supports these specifications.

IMPORTANT

You can special order a fiber cable in any length up to 2 km (1.24 mi) from

your fiber cable vendor.

Table 4 - Fiber Cable and LC Connector Specifications

Attribute

Value

Fiber transceiver type

100Base-FX IEEE802.3u

Optical wavelength

1310 nm no cap

Transmitter launch power at beginning of life (BOL), min

Allow -1 dB at end of life (EOL)

-19 dBm into 62.5/125 µm fiber, N/A = 0.275
-22.5 dBm into 50/125 µm fiber, N/A = 0.20

Receiver sensitivity, min

-31.8 dBm

Receiver sensitivity, max

-14 dBm