• The ADR scanner saves and restores only the configuration parameters

contained in the module’s EDS file. Some XM parameters are not
included in the EDS file because they are not supported by either the
EDS specification or the tools that read the EDS files, for example
RSNetWorx for DeviceNet. These configuration parameters will not be
restored with ADR.

Below is a list of the configuration parameters that are not included in
the EDS file and can not be saved or restored with ADR.

Channel Name
Tachometer Name
Alarm Name
Relay Name
All Triggered Trend related parameters
All SU/CD Trend related parameters
Custom Assembly structure

• The ADR and trigger group functions cannot be used together. A

module can have only one primary master so a module cannot be both
configured for ADR and included in a trigger group. The ADR scanner
must be the primary master for the modules configured for ADR. The
XM-440 Master Relay module must be the primary master for modules
included in a trigger group.