Rockwell Automation Publication GMSI10-UM009D-EN-P - June 2011

46 Configuration Parameters

Controls whether the relay must be explicitly reset
after the alarm subsides.

Activation Delay

Enter the length of time for which the relay
activation logic (Activate relay when parameter)
must be true before the relay is activated.

Enter a value from 0 to 25.5 seconds,
adjustable in increments of 0.1
seconds.

Default is 1 second

Sets the alarm conditions that will cause the relay to
activate. You can select more than one.

Normal - The current measurement is not in

within excess of any alarm thresholds.

Alert - The current measurement is in excess of

the alarm level threshold(s) but not in excess of the
danger level threshold(s).

Danger - The current measurement is in excess of

the danger level threshold(s).

Disarm-The alarm is disabled or the device is in

Program mode.

Xdcr (Transducer) Fault - A transducer fault is

detected on the associated transducer.

Module Fault - Hardware or firmware failure, or

an error has been detected and is preventing
proper operation of the device.

Tacho Fault - A required tachometer signal has

not been detected. Note that there is no
transducer fault either.

Unknown - The current alarm status cannot be

determined. This is useful when the XM-440 loses
its communication link and can no longer receive
the actual alarm status values.

Options: Normal

Danger
Xdcr Fault
Tacho Fault
Alert
Disarm
Module Fault
Unknown

Check to enable.
Clear to disable.

Relay Installed

Indicates whether the relay is a physical relay on a
module or a virtual relay. If the relay is a physical
relay, then you can set the Failsafe parameter.

If the relay is a virtual relay, the Failsafe parameter
is not used or it is disabled.

Relay Parameters

Parameter Name

Description

Options/Comments

XM Configuration
Utility

EDS File

Latching

Latching
Option

XM Configuration
Utility

EDS File

Check means
latching (relay must
be explicitly reset)

Latching

Clear means
non-latching (relay
is reset once the
alarm condition has
passed)

Nonlatching

XM Configuration
Utility

EDS File

Alarm Status to
Activate On

Alarm Levels

XM Configuration
Utility

EDS File

Check = Physical
Relay

Installed =
Physical Relay

Clear = Virtual Relay Not Installed =

Virtual Relay