Rockwell Automation Publication GMSI10-UM009D-EN-P - June 2011

Installing the XM-440 Master Relay Module 39

Network Status (NS) Indicator

Relay Indicators (4 in all)

Basic Operations

Powering Up the Module

The XM-440 performs a self-test at power-up. The self-test includes an LED
test and a device test. During the LED test, the indicators will be turned on
independently and in sequence for approximately 0.25 seconds.

The device test occurs after the LED test. The Module Status (MS) indicator is
used to indicate the status of the device self-test.

Color

State

Description

No color

Off

Module is not online.

• Module is autobauding.
• No power is applied to the module, look at Module

Status LED.

Green

Flashing

Module is online (DeviceNet) but no connections are
currently established.

Solid

Module is online with connections currently
established.

Red

Flashing

One or more I/O connections are in the Timed-Out
state.

Solid

Failed communications (Duplicate MAC ID or Bus-off).

Color

State

Description

Red

Off

On-board relay is not activated.

Solid

On-board relay is activated.

Device Self-Test Status

MS Indicator State

Description

Flashing Red and Green

Device self test is in progress.

Solid Green or Flashing Green

Device self test completed successfully, and the
firmware is valid and running.

Flashing Red

Device self test completed, the hardware is OK, but the
firmware is invalid. Or, the firmware download is in
progress.

Solid Red

Unrecoverable fault, hardware failure, or Boot Loader
program may be corrupted.