Data Structures and Expressions
A-5
initialized at the start of each scan from the loop auxiliary,
M_RESET.
MODE
Integer
Loop operating mode auxiliary:
0
Manual
1
Automatic
2
Cascade
M_RESET
Real
PID manual reset auxiliary
MSV
Real
The tag name of the value passed from the last scanned step.
M_FLG
Boolean
Manual flag. This loop is in automatic or cascade mode,
but was not on the previous scan.
OPHILM
Real
Loop output high limit auxiliary
OPLOLM
Real
Loop output low limit auxiliary
OUT
Real
Loop analog output auxiliary
PERIOD
Real
Loop scan time auxiliary
PRIMARY_FLG
Boolean
This controller is installed in the primary position.
PV
Real
Loop process variable auxiliary.
R_FLG
Boolean
Reset flat. This is the first scan of this loop
since power up reset or new configuration.
RATIO
Real
Ratio auxiliary for PID ratio and bias subfunctions.
SCAN_TIME
Real
The actual time in seconds since this loop was last scanned.
SPAN
Real
Loop span. This is used to convert process
value to a fraction in the PID algorithm.
SPHILM
Real
Upper limit of setpoint [100]
SPLOLM
Real
Lower limit of setpoint [0]
SP_CUR
Real
Current setpoint value
SP_RATE
Real
Setpoint ramp rate limit [100]
SP_TARG
Real
Target setpoint value
STATE
Integer
Current batch state from sequence control function.
STATE_TIME
Real
Length of time (minutes) in current batch
state while not held.
TOD
Integer
Time of day counter. May be converted to
engineering units (seconds, minutes...) using
the T_... time conversion expression functions.