Table 9-1, Characteristics performance – Rockwell Automation T6200 Compressor Anti-Surge and Capacity Controller User Manual
Page 172
Specifications
Table
9-1
T6200 Controller Electrical Characteristics (T6200”C” module)
Characteristics
Performance
Analog-To-Digital Conversion
Accuracy
Non-Linearity
Resolution
Noise
T6200C only
± 0.2% of full scale
± 0.05% of full scale
12-bits + sign
± 0.1% of full scale
Programmable Gain Amplifier
Gain
Settings
Accuracy G=1/2/4/8/16
T6200C only
1, 2, 4, 8 and 16
± 0.05% / ± 0.05% / ± 0.10% / ± 0.15% / ± 0.15%
Analog Inputs
Number of Inputs:
Signal
Types:Voltage
Current
Common Mode Rejection
Common Mode Protection
Input Res.:Voltage Mode
Current Mode
T6200C only
Up to 20
± 625 mVdc, ± 1.2 Vdc, ± 2.5 Vdc, ± 5 Vdc, and ± 10 Vdc, auto ranging
± 2.5 mAdc, ± 5 mAdc, ± 10 mAdc, and ± 20 mAdc, auto-ranging
80 dB @ 60 Hz (When configured as an isolated input)
100 V transient absorbers
800 k
Ω differential and 400 kΩ common mode
250
Ω +0/-0.04% differential and 400 kΩ common mode
When configured as an isolated input
Analog Outputs
Number of Outputs:
Signal
Type
Output
Load
Resolution
Accuracy
Non-Linearity
T6200C only
4 to 8
0-20 (4-20) mAdc, current sourcing
0-350
Ω; Larger resistance may be used, (see I/O Circuit Description)
12 bits
± 150
µ
A
± 10
µ
A
Discrete Inputs (On/Off)