Rockwell Automation FANM FanMaster Energy Saving Package User Manual
Page 50

3-14
FanMaster Configuration and Start Up
Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -
Publication FANM-IN001B-EN-P – December, 2009 PN-65329
Important: If, after completing the steps below, the following alarm
message displays, “Drive Parameter Write Failed”, do the
following:
•
Verify all communication wiring between the drive(s) and
FanMaster.
•
Verify the parameter settings for PowerFlex 70EC, 700VC or
753 drives as instructed below.
–
Setting the Parameters in a PowerFlex 70EC or 700VC Drive
(below).
–
Setting the Parameters in a PowerFlex 753 Drive on page 3-15
.
Setting the Parameters in a PowerFlex 70EC or 700VC Drive
Important: When removing power from the drive(s) as directed in the
steps on this screen, verify that the drive is fully
de-energized by waiting until the HIM module LED
display is off.
a. Press the ESC key (
) until the Main Menu displays (as shown
below).
b. Press the Down arrow key (
) to select “Device Select”.
c.
Press the Enter key (
).
d. Press the Down arrow key twice to select “20-COMM-H” in the
list.
e.
Press the Enter key.
f.
Press the Enter key again.
g. Press the Down arrow key once to view parameter 32 [RTU Param
Mode].
h. Press the Enter key.
i.
For PowerFlex 70EC drives, press the “0” key, for PowerFlex
700VC drive, press the “1” key.
j.
Press the Enter key.
k. Press the down arrow key twice to view parameter 30 [Stop Bits
Cfg].
l.
Press the Enter key.
m. Press the “0” key.
n. Press the Enter key.
o. Complete the next instruction as directed on the FanMaster screen.
Esc
Main Menu:
Diagnostics
Parameter
Device Select