Rockwell Automation FANM FanMaster Energy Saving Package User Manual
Page 103
FanMaster Screens and Field Descriptions
C-11
Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -
Publication FANM-IN001B-EN-P – December, 2009 PN-65329
Table C.J Cooling and Heating Setup Screen Fields
Heading Field Name
Description
Cooling Setup
Delta-T Min
The difference in temperature between the mixed air and supply air
at and below which the drive will run the supply fan at the minimum
speed when cooling the conditioned space.
Delta-T Max
The difference in temperature between the mixed air and supply air
at or above which the drive will run the supply fan at the maximum
speed when cooling the conditioned space.
VFD Output Min
The percentage of full speed that the drive will run the supply fan
when the temperature difference is at or below the minimum value
(in “Delta-T Min” for Cooling) when cooling the conditioned space.
VFD Output Max
The percentage of full speed that the drive will run the supply fan
when the temperature difference is at or above the maximum value
(in “Delta-T Max” for Cooling) when cooling the conditioned space.
SA Low Limit Override
Supply Air Low Limit The supply air low temperature limit below which FanMaster runs
the supply air fan at full speed (100%) in an attempt to avoid
freezing up the cooling system.
Heating Setup
Delta-T Min
The difference in temperature between the mixed air and supply air
at and below which the drive will run the supply fan at the minimum
speed when heating the conditioned space.
Delta-T Max
The difference in temperature between the mixed air and supply air
at or above which the drive will run the supply fan at the maximum
speed when heating the conditioned space.
VFD Output Min
The percentage of full speed that the drive will run the supply fan
when the temperature difference is at or below the minimum value
(in “Delta-T Min”) when heating the conditioned space.
VFD Output Max
The percentage of full speed that the drive will run the supply fan
when the temperature difference is at or above the maximum value
(in “Delta-T Max”) when heating the conditioned space.
SA High Limit Override
Supply Air High Limit The supply air high temperature limit above which FanMaster runs
the supply air fan at full speed (100%) in an attempt to avoid
overheating the heating system.
AHU
Press to view the
Air Handler Unit Diagram Screen
PNLVW
Config
Press to access the PanelView Configuration Main screen where you can choose to
upgrade the FanMaster PanelView application firmware.
Factory
Only
(Secured access setup for factory use only.)
Back
Press to view the
Fan Communication Setup Screen
Next
Press to view the
.