FanMaster Screens and Field Descriptions

C-11

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -

Publication FANM-IN001B-EN-P – December, 2009 PN-65329

Table C.J Cooling and Heating Setup Screen Fields

Heading Field Name

Description

Cooling Setup

Delta-T Min

The difference in temperature between the mixed air and supply air
at and below which the drive will run the supply fan at the minimum
speed when cooling the conditioned space.

Delta-T Max

The difference in temperature between the mixed air and supply air
at or above which the drive will run the supply fan at the maximum
speed when cooling the conditioned space.

VFD Output Min

The percentage of full speed that the drive will run the supply fan
when the temperature difference is at or below the minimum value
(in “Delta-T Min” for Cooling) when cooling the conditioned space.

VFD Output Max

The percentage of full speed that the drive will run the supply fan
when the temperature difference is at or above the maximum value
(in “Delta-T Max” for Cooling) when cooling the conditioned space.

SA Low Limit Override

Supply Air Low Limit The supply air low temperature limit below which FanMaster runs

the supply air fan at full speed (100%) in an attempt to avoid
freezing up the cooling system.

Heating Setup

Delta-T Min

The difference in temperature between the mixed air and supply air
at and below which the drive will run the supply fan at the minimum
speed when heating the conditioned space.

Delta-T Max

The difference in temperature between the mixed air and supply air
at or above which the drive will run the supply fan at the maximum
speed when heating the conditioned space.

VFD Output Min

The percentage of full speed that the drive will run the supply fan
when the temperature difference is at or below the minimum value
(in “Delta-T Min”) when heating the conditioned space.

VFD Output Max

The percentage of full speed that the drive will run the supply fan
when the temperature difference is at or above the maximum value
(in “Delta-T Max”) when heating the conditioned space.

SA High Limit Override

Supply Air High Limit The supply air high temperature limit above which FanMaster runs

the supply air fan at full speed (100%) in an attempt to avoid
overheating the heating system.

AHU

Press to view the

Air Handler Unit Diagram Screen

.

PNLVW
Config

Press to access the PanelView Configuration Main screen where you can choose to
upgrade the FanMaster PanelView application firmware.

Factory
Only

(Secured access setup for factory use only.)

Back

Press to view the

Fan Communication Setup Screen

.

Next

Press to view the

Proof of Flow Setup Screen

.