Appendix d, Fanmaster application firmware upgrades, Required equipment – Rockwell Automation FANM FanMaster Energy Saving Package User Manual
Page 111: Appendix

Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -
Publication FANM-IN001B-EN-P – December, 2009 PN-65329
Appendix
D
FanMaster Application Firmware Upgrades
Complete all steps in this appendix to upgrade your FanMaster MicroLogix
1100 and PanelView terminal application firmware.
Note: You may be required to upgrade the PanelView operating system
firmware to the latest available prior to upgrading the FanMaster PanelView
application firmware. The PanelView operating system must be version
1.11 or higher in order to run the FanMaster PanelView application version
2.00. The PanelView operating system firmware is present on the
PanelView operating system boot up screen visible at the initial application
of power to the unit. For information about downloading and installing the
PanelView operating system firmware upgrade,
Required Equipment
•
1763-MM1 - Memory Module for the MicroLogix 1100
pre-programmed with the FanMaster MicroLogix 1100 application
firmware.
•
USB “Thumb drive” pre-programmed with the FanMaster PanelView
application firmware.
Upgrade the FanMaster
MicroLogix 1100 Controller
Application Firmware
Important: All configuration data will be set to the default values after the
firmware upgrade has been completed.
1. Turn off the Air Handler Unit (AHU) so FanMaster does not receive any
“run” signals while the supply air fan (and return air fan, if installed) is
off. If a bypass is installed on the drive, you can set the drive to bypass if
you want to allow the fan(s) to run during the firmware upgrade
procedure.
2. Record all FanMaster configuration data. If you have not previously
recorded your configuration data, or it has changed since you installed
FanMaster, use the chart in
Gather and Record Data on page 3-2
to do
so.
3. Stop data logging and clear the log. See