Rockwell Automation FANM FanMaster Energy Saving Package User Manual
Page 39

FanMaster Configuration and Start Up
3-3
Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual -
Publication FANM-IN001B-EN-P – December, 2009 PN-65329
49d The percentage of full speed that the drive will run the supply fan when the temperature
difference is at or above the maximum value when cooling the conditioned space.
100
49a The difference in temperature between the mixed air and supply air at or below which the
drive will run the supply fan at the minimum speed when heating the conditioned space.
5
50b The difference in temperature between the mixed air and supply air at or above which the
drive will run the supply fan at the maximum speed when heating the conditioned space.
50
50c The percentage of full speed that the drive will run the supply fan when the temperature
difference is at or below the minimum value when heating the conditioned space.
50
50d The percentage of full speed that the drive will run the supply fan when the temperature
difference is at or above the maximum value when heating the conditioned space.
100
51
The supply air low temperature limit at which FanMaster will command the supply fan speed
to run at full speed to avoid freezing up the cooling system.
45
52
The supply air high temperature limit at which FanMaster will command the supply fan to run
at full speed to avoid overheating the heating system.
145
Step Data Required
Default Value
Actual