A-2
Super Remote Meter Interface (RMI) Board
Isolated Digital Outputs
Number:
4
Features:
Programmable, source-driven (active high with
common ground) and short circuit-protected.
Range:
24 VDC, 20 mA per output (jumper setting
: 24 V INT)
100 mA per output with external power supply
(jumper setting
: 24 V EXT)
Update time:
1.0 ms if delay time = 0
100.0 ms if delay time
≠
0
Relay Outputs
Number:
3
Features:
Three relays, programmable, timer function.
Relay 1 has a normally-open contact.
Relays 2 and 3 have 1 normally-open and 1
normally-closed contact.
Rating:
2 A, 24VDC or 250VA, 120VAC
Update time:
1.0 ms if delay time = 0
100.0 ms if delay time
≠
0
Isolated Analog Outputs
Number:
3
Features:
Short circuit-protected, programmable,
software-calibrated.
Range:
Output 1:
0 to 10 VDC
Output 2:
–0 to +10VDC
Output 3:
0 to 10 VDC (jumper setting
: V OUT)
0 to 20 mA (jumper setting
: C OUT)
Load:
10 VDC outputs: RL
≥
10 k
Ω
20 mA output: RL
≤
500
Ω
Crossover frequency:
1 kHz
Carrier frequency:
20 kHz
Resolution:
10 bits
Connection Port to the Regulator Board
34-pin flat cable connector
Power Consumption of the RMI Board
24 V supply current:
Max. 320 mA with unloaded digital outputs
Additional load:
Max. 20 mA load current per digital output (4 total)
External 24 V supply:
For 20 mA < load current < 100 mA, an external 24
V power supply must be connected to terminals 46
(+) and 51 (–) and the 24V jumper must be set to
24 V EXT.
15 V
Not used.