4-10
Super Remote Meter Interface (RMI) Board
r.030 Digital Input Configuration
(Continued)
8 Presets
If r.030 = 8, one of Preset Speeds P.031 to P.038 is selected by DIGIN 2 to DIGIN 4.
See table 4.4.
The RMI board's digital and relay outputs are turned on or off as a function of 20
possible comparisons. The values in r.031 through r.037 select the comparison to use
for a particular output.
Table 4.4 – Preset Speed Digital Inputs
Digital Inputs (Terminals)
Selected
Speed Reference
DIGIN 4 (44)
DIGIN 3 (43)
DIGIN 2 (42)
OFF
OFF
OFF
P.031
OFF
OFF
ON
P.032
OFF
ON
OFF
P.033
OFF
ON
ON
P.034
ON
OFF
OFF
P.035
ON
OFF
ON
P.036
ON
ON
OFF
P.037
ON
ON
ON
P.038
r.031 to r.037 Digital Output and Relay Outputs Configuration
Par.
Parameter Name
Type
Default
Step
Range
r.031
Digital Output 1 Configuration
Config.
0
1
0 to 21 (Table 4.5)
r.032
Digital Output 2 Configuration
r.033
Digital Output 3 Configuration
r.034
Digital Output 4 Configuration
r.035
Relay Output 1 (NO) Configuration
r.036
Relay Output 2 (NO/NC) Configuration
r.037
Relay Output 3 (NO/NC) Configuration
Table 4.5 – Digital Outputs and Relay Outputs Configuration Selections
Selection
Description
Update Time
0 = Not Used
The output is always off.
N/A
1 = Running
The output is turned on when the drive is in run.
20 ms
2 = Fault
The output is turned on when there is a fault.
20 ms
3 = Aux Input 1
The output is turned on or off (time delayed) as a function
of the Aux 1 input (digital input 4). If digital input 4 is not
programmed as Aux 1, the output will be off.
100 ms