Rockwell Automation GV3000/SE, VTAC 7 Super Remote Meter Interface Board M/N 2SI3000 M/N 2SI3000E User Manual
Page 72

4-14
Super Remote Meter Interface (RMI) Board
The RMI board's digital and relay outputs can be individually programmed for on-delay
or off-delay. After the regulator signals an output to turn on or off, the RMI board will
wait for the programmed time delay before the output is turned on or off.
20 = Speed Reference
The output is turned on when the absolute value of the
selected speed reference is greater than or equal to Low
Speed Detection (r.056). The output is turned off when
the absolute value of the selected speed reference is less
than the value in r.056 minus the Speed Detection
Hysteresis Band (r.053).
Figure 4.10 – Speed Reference
21 = TB Start & Stop
The output is turned on when the terminal block Start and
Stop inputs are both closed. The output is turned off
when either of these inputs is open.
r.040 to r.046 Digital Output Relay Timers
Par.
Parameter Name
Type
Default
Step
Range
r.040
Digital Output 1 Delay Time
Tunable
0 sec
0.1
–999.9 to 999.9 sec
+ on-delay values
– off-delay values
r.041
Digital Output 2 Delay Time
r.042
Digital Output 3 Delay Time
r.043
Digital Output 4 Delay Time
r.044
Relay Output 1 Delay Time
r.045
Relay Output 2 Delay Time
r.046
Relay Output 3 Delay Time
Table 4.5 – Digital Outputs and Relay Outputs Configuration Selections (Continued)
Selection
Description
Update Time
RQVWDWH
6HOHFWHG 6SHHG 5HIHUHQFH
RIIVWDWH
/
+
/ /HYHO U
+ +\VWHUHVLV U