Installing Your Monitor
11
Publication 6185-UM003C-EN-P
Panel Mounting Guidelines
Observe the following precautions before installing the unit in a panel:
• Confirm that there is adequate space behind the panel.
Allow at least 1.0” (26mm) on the sides and bottom and 2.0” (51mm)
on the top ventilation.
− For a 6185-H (15” panel mount), a cabinet with a minimum depth
of 2.9 in. (74mm) is sufficient.
− For a 6185-J (17” panel mount), a cabinet with a minimum depth
of 3.0 in. (76mm) is sufficient
• Take precautions so that metal cuttings do not enter any components
that are already installed in the panel.
• Supporting panels should be at least 14 gauge to ensure proper
sealing against water and dust and to provide proper support. The
mounting hardware supplied accommodates panels up to 0.25 in.
(6.35 mm) thick.
Note:
Supporting panels must be cut and drilled to
specifications before installation.
ATTENTION: Failure to follow these warnings may
result in personal injury or damage to the panel
components.