Chapter 4
Status Displays
4–9
This display shows the progress of the loading operation of the A-B VBASIC
program on the top line and the date/time of the loading operation on the
lower line.
Figure 4.9
Program Load Status, Display 7
LOAD STATUS
MSG
AT
hhmmss
yymmdd
Program Load Messages that could appear on the top line are:
Never loaded
This message appears from the time the workstation
is set to factory defaults until the arrival of a
program record.
Loading Line: xx
This message is shown as each program record is
received. It should take only a few moments at most
to load a program. If this line is not being updated
every few seconds, the download operation has been
interrupted, possibly by a communications protocol
error from the Host computer.
Loaded
This message indicates that the A-B VBASIC
program was loaded without error and started. The
PC program name is shown. Note: This does not
imply that the program loaded is currently running.
For workstation run status, check status display
eight.
Load Sequence xx –
This message indicates that at least one of the
records of the program was received in the wrong
order. The ‘xx’ indicates the expected record.
Length Counters! –
This message indicates that the counters holding the
size of the program’s pseudo-code and array
descriptions do not equal the total program length
counter.
Load Length! –
This message says the amount of pseudo-code
received does not equal the number supplied in the
total length count.
Program Checksum – This message says the checksum of the pseudo-code
does not equal the value expected.
Program Load Status