Chapter 5
Maintenance and Troubleshooting
5–4
A TEST button is located on the front of the module. When you press and
hold this button, the module enters test mode. Two tests are run.
1. Lamp / LED Test
All push button lamps and red/green LEDs turn OFF for one second, then
illuminate for two seconds. If you press the TEST button when the test is
done, the module continues with the Push Button Contact test.
2. Push Button Contact Test
Push buttons react as shown in Table 5A.
Selector switches react as shown in Table 5B.
During TEST mode, the status of the lamps are not updated, and any push
button presses are not transmitted to the PLC. The module exits test mode
two seconds after you release test button.
Table 5.A
Testing the Contacts of Illuminated Push Buttons
Push Button Lamp
Description
800A
NEMA 4
800EM/EP and 800T/H
N.O. Contacts N.C. Contacts
Non-actuated
ON
ON
ON
OFF
Actuated
OFF
OFF
OFF
ON
Contact Failure
Flashing
–
–
–
Table 5.B
Testing the Contacts of Illuminated Selector Switches
Contact A
Lamp
Typical Example
800T-JR2KB7AXZ3
Open
ON
or
Closed
Off
To test 4 position selector switch inputs and other non-illuminated push
button and selector switch inputs, release the TEST button on the module and
examine the corresponding Input Image Table locations while operating.
Make sure the controller is in TEST mode before operating buttons.
Additional Test for 800A Push Button Modules
Hold the push-to-test button in while power is applied to module. If a push
button causes a fault, the lamp in that push button will flash.