Page 65

Chapter 4
Programming the RediPANEL Modules
4–26
The scanner input file is shown below. The output file is similar; it is
addressed O:1.0 to O:1.3
Rack 3 Group 6
Rack 3 Group 7
Rack 1 Group 2
Rack 1 Group 3
Rack 1 Group 0
Rack 1 Group 1
Rack 1 Group 6
Rack 1 Group 4
Rack 1 Group 5
Rack 0 Group 6
Rack 0 Group 7
Rack 0 Group 4
Rack 0 Group 5
Rack 0 Group 2
Rack 0 Group 3
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Bit Number
Input File
I:1.0
I:1.1
I:1.2
I:1.3
I:1.4
I:1.5
I:1.6
I:1.7
I:1.8
I:1.9
I:1.10
I:1.11
I:1.12
I:1.13
I:1.14
I:1.30
I:1.31
Word 0
Word 1
Word 2
Word 3
Word 4
Word 7
Word 8
Word 9
Word 10
Word 11
Word 12
Word 13
Word 14
Word 5
Word 6
Word 30
Word 31
Rack 0 Group 0
Rack 0 Group 1
Rack 3 Group 1
Rack 3 Group 2
Rack 2 Group 7
Rack 3 Group 0
Rack 3 Group 5
Rack 3 Group 3
Rack 3 Group 4
Rack 2 Group 5
Rack 2 Group 6
Rack 2 Group 3
Rack 2 Group 4
Rack 2 Group 1
Rack 2 Group 2
I:1.15
I:1.16
I:1.17
I:1.18
I:1.19
I:1.20
I:1.21
I:1.22
I:1.23
I:1.24
I:1.25
I:1.26
I:1.27
I:1.28
I:1.29
Word 15
Word 16
Word 17
Word 18
Word 19
Word 22
Word 23
Word 24
Word 25
Word 26
Word 27
Word 28
Word 29
Word 20
Word 21
Rack 1 Group 7
Rack 2 Group 0
Rack 0
Rack 1
Rack 2
Rack 3
RediPANEL
0
8
1
8
2
8
3
8
4
8
5
8
6
8
7
8
10
8
11
8
12
8
13
8
14
8
15
8
16
8
17
8
Bit Number (octal)
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
not used
The BAUD rate is 115.2K. DIP. Switch 1 must be in the OFF position; DIP
switch 2 must be ON.
The G file size is set to 3 using the Speciality I/O Configuration function.
The M0 and M1 file sizes are set to 32 in the Advanced Set Up function.
Since only the first 4 words of the input and output files contain valid
information, the scanned input and output words can be set to 4. Reducing
the number of scanned input and output words decreases SLC scan time.
Configuration information is entered in the Modify G File function. Word 0
is reserved and cannot be modified. Word 1 indicates the starting address of
the device, word 2 indicates its size.