Publication 1797-6.5.6 - June 2005

13-4 1797-IJ2 FLEX Ex Frequency Input Module

Channel 1 Frequency Input

Field devices may only be connected to the terminals of one of the five
following circuits. The terminals of the remaining four circuits must not be
connected.

Namur/Con
tact
(terminals
9-8)

Protection

Group

Allowed
Capacitance

Allowed
Inductance

L

o

R

o

Ratio

U

o

= 14.7V

I

o

= 15mA

P

o

= 30mW

EEx ia

IIB

3.86

µF

300mH

2.6mH/

IIC

620nF

80mH

0.65mH/

Magnetic
500mV
(terminals
10-12)

Protection

Group

Allowed
Capacitance

Allowed
Inductance

L

o

R

o

Ratio

U

o

= 14.7V

I

o

= 10mA

P

o

= 18mW

EEx ia

IIB

3.86

µF

600mH

4.15mH/

IIC

620nF

150mH

1.03mH/

Magnetic
50mV
(terminals
10-12,
9-11)

Protection

Group

Allowed
Capacitance

Allowed
Inductance

L

o

R

o

Ratio

U

o

= 14.7V

I

o

= 10mA

P

o

= 18mW

EEx ia

IIB

3.86

µF

600mH

4.15mH/

IIC

620nF

150mH

1.03mH/

Vortex 6V
(terminals
14, 13-12)

Protection

Group

Allowed
Capacitance

Allowed
Inductance

L

o

R

o

Ratio

U

o

= 26.5V

I

o

= 82mA

P

o

= 520mW

EEx ia

IIB

730nF

8mH

0.26mH/

IIC

95nF

2mH

0.06mH/

Vortex 3V
(terminals
15, 13-12

Protection

Group

Allowed
Capacitance

Allowed
Inductance

L

o

R

o

Ratio

U

o

= 26.5V

I

o

= 82mA

P

o

= 520mW

EEx ia

IIB

730nF

8mH

0.26mH/

IIC

95nF

2mH

0.06mH/