Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual
Page 157

Publication 1797-6.5.6 - June 2005
1797-IJ2 FLEX Ex Frequency Input Module 32-5
The entity concept allows interconnection of intrinsically safe apparatus
with associated apparatus not specifically examined in combination as a system
when the approved values of V
oc
and I
sc
or V
t
and I
t
of the associated apparatus
are less than or equal to V
max
and I
max
of the intrinsically safe apparatus and the
approved values of C
a
and L
a
of the associated apparatus are greater than C
i
+
C
cable
and L
i
+ L
cable
respectively for the intrinsically safe apparatus.
Simple apparatus is defined as a device which neither generates nor stores
more than 1.2V, 0.1A, 20µJ, or 25mW.
Wiring methods must be in accordance with the National Electric Code,
ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA
C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA
RP12.6.
This module, 1797-IJ2, must be used with terminal base 1797-TB3 or
1797-TB3S.
Terminals 19, 30, 36, 38-39, and 47-49 shall not be connected.
WARNING: Substitution of components may impair intrinsic safety.
AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.
The ambient operating temperature (T
amb
) for this product is -20°C to
70°C.
Suitable for Class II, Division1, Groups E, F, G and Class III when
mounted in a UL listed Type 4, 4X, 6, 6P, 9, 12, or 12K enclosure.