Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual
Page 142
Publication 1797-6.5.6 - June 2005
29-4 1797-OE8 FLEX Ex 8 Output Analog Module
Table 2: Flexbus Entity Values Which are Allowed for the Next
FLEX Ex I/O Module
Table 3: Flexbus Entity Values for this Module
Note: Any combination of up to eight FLEX Ex I/O modules may be
attached on a flexbus.
The entity concept allows interconnection of intrinsically safe apparatus
with associated apparatus not specifically examined in combination as a system
when the approved values of V
oc
and I
sc
or V
t
and I
t
of the associated apparatus
are less than or equal to V
max
and I
max
of the intrinsically safe apparatus and the
approved values of C
a
and L
a
of the associated apparatus are greater than C
i
+
C
cable
and L
i
+ L
cable
respectively for the intrinsically safe apparatus.
Simple apparatus is defined as a device which neither generates nor stores
more than 1.2V, 0.1A, 20µJ, or 25mW.
Wiring methods must be in accordance with the National Electric Code,
ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA
C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA
RP12.6.
This module, 1797-IE8, must be used with terminal base 1797-TB3 or
1797-TB3S.
Terminals 2, 3, 6, 7, 10, 11, 14, 15, 19, 20, 23, 24, 27, 28, 31, 32, 36-39, and
46-49 shall not be connected.
WARNING: Substitution of components may impair intrinsic safety.
AVERTISSEMENT: La substitution de composant peut compromettre la
securite intrinseque.
The ambient operating temperature (T
amb
) for this product is -20°C to
70°C.
Suitable for Class II, Division1, Groups E, F, G and Class III when
mounted in a UL listed Type 4, 4X, 6, 6P, 9, 12, or 12K enclosure.
Terminals
V
t
(V)
I
t
(mA)
Groups
C
a
(
µF)
L
a
(
µH)
Male Bus
Connector
5.8
400
A-G
IIC, IIB, IIA
3.0
3.0
Terminals
V
max
(V)
I
max
(mA)
Groups
C
i
(
µF)
L
i
(
µH)
Female Bus
Connector
5.8
400
A-G
IIC, IIB, IIA
1.35
0