Wiring to a 1797-tb3 or -tb3s terminal base unit, Intrinsically safe specifications, Connect wiring to the terminal base as shown below – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual
Page 74
Publication 1797-6.5.6 - June 2005
13-2 1797-IJ2 FLEX Ex Frequency Input Module
Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
Intrinsically Safe
Specifications
For a full list of specifications, refer to FLEX Ex Frequency Input Module
Installation Instructions, publication 1797-5.7.
Row A
Row B
Row C
+V
-V
42334
3V
V+
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
6V
GND 50
mV
Sel
N
500/50
mV
8V
8V N
GND
6V
V+
3V
R0 NO R0 NC
-V
No connection allowed to terminals 19, 30, 36, 38, 39, 47, 48, 49
+V
R0 COM
R1 COM
50
mV
Sel
500/50
mV
Channel 0 Frequency Input
Channel 1 Frequency Input
GND
GND 50
mV
Sel
N
500/50
mV
8V
8V N
50
mV
Sel
500/50
mV
GND
R1 NO R1 NC
Channel 0 Gate Input
Channel 1 Gate Input
ATTENTION
Do not use any unused terminals on this terminal base unit.
Using these terminals as supporting terminals can result in
damage to the module and/or unintended operation of
your system.
Output (intrinsically safe)
(16 position male/female flexbus
connector)
U
o
< 5.8V
I
o
< 400mA
Li = Negligible
Ci < 2.64
µF
Power Supply
(+V, -V Intrinsically Safe)
U
i
< 9.5V dc
I
i
< 1A
L
i
= Negligible
C
i
= Negligible
Operating Temperature
-20 to +70
o
C (-4 to +158
o
F)
Agency Certification
II (1) 2G EEx ia/ib IIB/IIC T4
II (1D) (2D)
Certificates
DMT 98 ATEX E 033 X