1797-PS1N FLEX Ex Power Supply 33-3

The entity concept allows interconnection of intrinsically safe apparatus

with associated apparatus not specifically examined in combination as a system
when the approved values of V

oc

and I

sc

of the associated apparatus are less

than or equal to V

max

and I

max

of the intrinsically safe apparatus and the

approved values of C

a

and L

a

of the associated apparatus are greater than C

i

+

C

cable

and L

i

+ L

cable

respectively for the intrinsically safe apparatus.

Wiring methods must be in accordance with the NEC, ANSI/NFPA 70,

Article 504 or the CEC CSA C22.1, Part 1, Appendix F. For additional
information refer to ANSI/ISA RP12.6.

Wiring methods must be in accordance with the NEC, ANSI/NFPA 70,

Article 501 or the CEC CSA C22.1, Part 1, Section 18.

For mounting of the power supply, conduit runs must have sealing fittings

connected within 6 inches of enclosure.

Ch4
Ch3
Ch2

Ch1

1 2 3 4 5

17
16
15
14
13
12
11
10

11

12

Nonhazardous Location

Hazardous (Classified) Location

1797-PS1N

Class I, Division 1, Groups A, B, C, D

Class II, Division 1, Groups E, F, G

Class III, Division 1

power
supply

Hazardous (Classified) Location

Class I, Division 1, Groups A, B, C, D

Class II, Division 1, Groups E, F, G

Class III Division 1

nonintrinsically safe wiring

intrinsically safe wiring

To any IS device with entity
concept parameters of
(V

max

, I

max

, C

i

, L

i

) appropriate

for connection to associated
apparatus with entity
concept parameters listed in
Table 1: Entity Values for
Field Device Connections.

42101