Intrinsically safe specifications, Fm i/o entity parameters (each channel), Wiring methods – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual
Page 192: Operating temperature -20 to +70, C (-4 to +158, Wiring method channel terminals v, V) i, Ma) v, Ma) groups c, Μ f) l
![background image](/manuals/580372/192/background.png)
Publication 1797-6.5.6 - June 2005
42-2 1797-IBN16 FLEX Ex 16 NAMUR Input Module
Intrinsically Safe
Specifications
For a full list of specifications, refer to FLEX Ex 16 NAMUR Input Module
Installation Instructions, publication 1797-5.7.
FM I/O Entity Parameters
(Each Channel)
Wiring Methods
• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code
(NEC).
Table 1: Entity Values for Field Device Connections
Operating Temperature
-20 to +70
o
C (-4 to +158
o
F)
Agency Certification
Class I Division 1 Groups A-D T4
Class I Zone 1 AEx ib/[ia] IIC T4
Certificates
FM Certificate Number 3009806
FM
Wiring
Method
Channel Terminals
V
oc
(V)
I
sc
(mA)
V
t
(V)
I
t
(mA)
Groups
C
a
(
µF)
L
a
(mH)
1 and 2 Any one
channel
e.g. ch0
0(+), 1(-)
14.5 15
-
-
A, B
0.3
80.0
C, E
0.9
320.0
D, F, G
2.4
640.0
1797- IBN16
Allen-Bradley
B
-
A
7
PWR
6
5
4
3
2
1
0
9
8
11
10
13
12
15
14
6
16 Point NAMUR Input Module
6
FLEX Ex NAMUR
Input I/O Module
LEDs
Female Bus
Connection
Field Wiring
Terminals
Terminal
Base
Terminal
Base Key
Male Bus
Connection
Key Position for
Terminal Base
Insertion
42060