Wiring to a 1797-tb3 or -tb3s terminal base unit, Intrinsically safe specifications, Connect wiring to the terminal base as shown below – Rockwell Automation 1797-XXX FLEX Ex System Certification Reference Manual User Manual
Page 58
Publication 1797-6.5.6 - June 2005
8-2 1797-IE8H FLEX Ex 8 Input HART Analog Module
Wiring to a 1797-TB3 or
-TB3S Terminal Base Unit
Connect wiring to the terminal base as shown below.
Intrinsically Safe
Specifications
For a full list of specifications, refer to FLEX Ex Analog Input Modules
Installation Instructions, publication 1797-5.5.
Row A
Row B
Row C
+
-
+
-
+
-
+
-
Ch 7
Ch 6
Ch 5
Ch 4
+V -V
+V -V
40071
sig
sig
sig
sig
No connection
allowed
No connection
allowed
Ch 7
+
-
+
-
+
-
+
-
Ch 2
Ch 1
Ch 0
sig
sig
sig
sig
Ch 3
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
ATTENTION
Do not use any unused terminals on this terminal base unit.
Using these terminals as supporting terminals can result in
damage to the module and/or unintended operation of
your system.
Output (intrinsically safe)
(16 position male/female flexbus
connector)
U
i
< 5.8V
I
i
< 400mA
L
i
= Negligible
C
i
< 1.35
µF
Power Supply
(+V, -V Intrinsically Safe)
U
i
< 9.5V dc
I
i
< 1A
L
i
= Negligible
C
i
= Negligible
Operating Temperature
-20 to +70
o
C (-4 to +158
o
F)
Agency Certification
II (1) 2G EEx ia/ib IIB/IIC T4
II (1D) (2D)
Certificates
DMT 98 ATEX E 020 X