Choose a qualifier for an action – Rockwell Automation Logix5000 Controllers Sequential Function Charts Programming Manual User Manual
Page 29
![background image](/manuals/579930/29/background.png)
Design a sequential function chart Chapter 1
Each action (non-Boolean and Boolean) uses a qualifier to determine when it
starts and stops.
The default qualifier is N Non-Stored. The action starts when the step is activated
and stops when the step is deactivated.
To change when an action starts or stops, assign a different qualifier.
If you want the action to
And
Then assign this
qualifier
Which means
Start when the step is activated
Stop when the step is deactivated
N
Non-Stored
Execute only once
P1
Pulse (Rising
Edge)
Stop before the step is deactivated or when the step is deactivated
L
Time Limited
Stay active until a Reset action turns off this action
S
Stored
Stay active until a Reset action turns off this action
Or a specific time expires, even if the step is deactivated
SL
Stored and Time
Limited
Start a specific time after the step is activated and the
step is still active
Stop when the step is deactivated
D
Time Delayed
Stay active until a Reset action turns off this action
DS
Delayed and
Stored
Start a specific time after the step is activated, even if
the step is deactivated before this time
Stay active until a Reset action turns off this action
SD
Stored and Time
Delayed
Execute once when the step is activated
Execute once when the step is deactivated
P
Pulse
Start when the step is deactivated
Execute only once
P0
Pulse (Falling
Edge)
Turn off (reset) a stored action
• S Stored
• SL Stored and Time Limited
• DS Delayed and Stored
• SD Stored and Time Delayed
---------------------------------------------------->
R
Reset
Choose a qualifier for an
action