1-4 SIL Policy

Calibration of analog input and output modules to verify that accurate
data is obtained from and used on the modules.

For more information on system proof tests, see Publication

1756-RM001

. For

more information on the necessary I/O module, see Table 1.1.

IMPORTANT

Users’ specific applications will determine the timeframe
for the proof test interval.

However, keep in mind that the Probability of Failure on
Demand (PFD) calculations listed in Table 1.2 on page 1-8
use a proof test interval of once per year. If the proof test
interval is changed, the information must be recalculated.