A - failure estimates, Failure estimates, Appendix – Rockwell Automation 1794 FLEX I/O System with ControlLogix for SIL2 User Manual
Page 47
1
Publication 1794-RM001G-EN-P - December 2011
Appendix
A
Failure Estimates
The following tables list the failure estimates for the FLEX I/O products
included in this manual for different proof test intervals.
Table A.1 MTBF Field Data and Per Module PFD Estimates - T
1
= 1 year
Catalog Number:
Description:
(MTBF)
(1)
λ
(3)
Estimated PFD
1oo2
1794-ACN15
ControlNet Single Media Adapter
8,223,684
1.22E-07
2.15E-06
1794-ACNR15
ControlNet Redundant Media Adapter
8,223,684
1.22E-07
2.15E-06
1794-AENT
10/100Mb Ethernet Communication Adapter
691,134
1.45E-06
2.76E-05
1794-AENTR
10/100Mb Ethernet Redundant Communication Adapter
1,268,070
7.89E-07
1.45E-05
1794-IB10XOB6
10 Input/6 Output Module
4,943,442
2.02E-07
3.60E-06
1794-IB16
16 Sink Input Module
4,105,090
2.44E-07
4.34E-06
1794-IE8
Analog Input Module
37,952,679
2.63E-08
4.64E-07
1794-IF2XOF2I
Isolated Analog Input/Output Module
25,296,960
3.95E-08
6.97E-07
1794-IF4I
Isolated Analog Input Module
11,746,343
8.51E-08
1.50E-06
1794-IJ2
Frequency Counter Module
2,418,321
4.14E-07
7.45E-06
1794-IP4
Pulse Counter Module
2,375,360
4.21E-07
7.58E-06
1794-IR8
RTD Input Module
6,191,655
1.62E-07
2.87E-06
1794-IRT8
TC/RTD/mV Input Module
1,182,438
8.46E-07
1.56E-05
1794-IT8
Thermocouple Input Module
1,564,324
6.39E-07
1.17E-05
1794-OB16
16 Source Output Module
1,883,594
5.31E-07
9.62E-06
1794-OB16P
Protected Output Module
2,135,280
4.68E-07
8.46E-06
1794-OB8EP
Protected Output Module
2,389,669
(2)
4.18E-07
7.54E-06
1794-OE4
Analog Output Module
23,807,086
4.20E-08
7.41E-07
1794-OF4I
Isolated Analog Output Module
7,191,128
1.39E-07
2.47E-06
1794-OW8
Relay Output Module
14,766,876
6.77E-08
1.20E-06
1794-TB3
Terminal Base Units
21,128,346
(2)
4.73E-08
8.35E-07
1794-TB3G
Generic Terminal Base Units
27,320,800
3.66E-08
6.45E-07
1794-TB3GS
Generic Terminal Base Units
46,425,600
2.15E-08
3.79E-07
1794-TB3S
Terminal Base Unit
71,433,747
(2)
1.40E-08
2.46E-07
1794-TB3T
Temperature Terminal Base Units
73,096,226
(2)
1.37E-08
2.41E-07
1794-TB3TS
Temperature Terminal Base Units
75,763,399
(2)
1.32E-08
2.32E-07
1794-TBN
Terminal Base Units
75,716,615
1.32E-08
2.32E-07
1794-TBNF
Fused Terminal Base Units
4,812,320
(2)
2.08E-07
3.70E-06
1794-ACNR15XT
ControlNet Redundant Media Adapter
8,223,684
1.22E-07
2.15E-06