Publication 1794-RM001G-EN-P - December 2011

Failure Estimates A-9

1794-OB16P

Protected Output Module

2,135,280

4.68E-07

4.21E-09

1794-OB8EP

Protected Output Module

2,389,669

(2)

4.18E-07

3.68E-09

1794-OE4

Analog Output Module

23,807,086

4.20E-08

3.02E-10

1794-OF4I

Isolated Analog Output Module

7,191,128

1.39E-07

3.76E-10

1794-OW8

Relay Output Module

14,766,876

6.77E-08

4.94E-10

1794-TB3

Terminal Base Units

21,128,346

(2)

4.73E-08

3.41E-10

1794-TB3G

Generic Terminal Base Units

27,320,800

3.66E-08

2.62E-10

1794-TB3GS

Generic Terminal Base Units

46,425,600

2.15E-08

1.53E-10

1794-TB3S

Terminal Base Unit

71,433,747

(2)

1.40E-08

9.88E-11

1794-TB3T

Temperature Terminal Base Units

73,096,226

(2)

1.37E-08

9.66E-11

1794-TB3TS

Temperature Terminal Base Units

75,763,399

(2)

1.32E-08

9.31E-11

1794-TBN

Terminal Base Units

75,716.615

1.32E-08

9.32E-11

1794-TBNF

Fused Terminal Base Units

4,812,320

(2)

2.08E-07

1.64E-09

1794-ACNR15XT

ControlNet Redundant Media Adapter

8,223,684

1.22E-07

9.14E-10

1794-AENTRXT

10/100Mb Ethernet Redundant Communication Adapter

1,268,070

7.89E-07

8.17E-09

1794-OB8EPXT

8 Protected Output Module

14,771,049

6.77E-08

4.93E-10

1794-IB16XT

16 Sink Input Module

35,587,189

2.81E-08

2.00E-10

1794-OB16PXT

16 Protected Output Module

26,709,401

3.74E-08

2.68E-10

1794-IB10XOB6XT

10 Input/6 Output Combo Module

22,202,487

4.50E-08

3.24E-10

1794-OW8XT

8 Relay Output Module

18,518,519

5.40E-08

3.90E-10

1794-IE4XOE2XT

4 Input/2 Output Analog Combo Module

11,800,802

8.47E-08

6.24E-10

1794-IE8XT

8 Input analog Module

14,041,000

7.12E-08

5.20E-10

1794-OE4XT

4 Output Analog Module

11,381,744

8.79E-08

6.48E-10

1794-IF2XOF2IXT

2 Input/2 Output Isolated Analog Combo Module

6,317,918

1.58E-07

1.21E-09

1794-IF4IXT

4 Isolated Input Analog Module

7,297,140

1.37E-07

1.04E-09

1794-IF4ICFXT

4 Isolated Input Analog Module

7,297,140

1.37E-07

1.04E-09

1794-OF4IXT

4 Isolated Output Analog Module

5,493,902

1.82E-07

1.42E-09

1794-IJ2XT

2 Ch. Frequency Counter Module

11,714,128

8.54E-08

6.29E-10

1794-IRT8XT

8 TC/RTD Input Analog Module

8,204,792

1.22E-07

9.16E-10

(1)

MTBF measured in hours.

(2)

Calculated using field-based values for components

(3)

λ

= Failure Rate = 1 / MTBF

Table A.6 MTBF Field Data and Per Module PFH Estimates - T

1

= 5 years

Catalog Number:

Description:

(MTBF)

(1)

λ

(3)

Estimated
PFH 1oo2