beautypg.com

Rockwell Automation 1794 FLEX I/O System with ControlLogix for SIL2 User Manual

Page 26

background image

Publication 1794-RM001G-EN-P - December 2011

3-4 FLEX I/O Modules

The control, diagnostics and alarming functions must be performed in
sequence. For more information on faults, see publication

1756-RM001

.

General Considerations when using Any FLEX I/O Digital Output
Module

Regardless of the type of FLEX I/O output module used, there are a number
of general application considerations that you must follow when applying
these modules in a SIL2 application:

Proof Tests - Periodically (for example, once every several years) a
System Validation test must be performed. Manually, or automatically,
test outputs to make sure that all outputs are operational and not stuck
in the ON or OFF state. Outputs must be cycled from ON to OFF or
OFF to ON. For additional information, refer to publication

1756-RM001

.

Figure 3.4

The control, diagnostics and alarming functions must be performed in
sequence..

Use of external Relays to disconnect Module Power if Output
De-energization is Critical
: To make sure outputs will de-energize,
users must wire an external method that can remove power from the
actuator if a short or other fault is detected.

Test outputs at specific times to make sure they are operating
properly
. The method and frequency of testing is determined by the
type of module.

Timer done

Output Bit

Output Bit

Timer

Fault

Application Logic

Actuator

Alarm to Operator

Fault

Monitoring Input

Monitoring Input

Output Fault