Table 1.4 shows an example of a PFD calculation for a safety loop involving
two DC input modules used in a 1oo2 configuration and a DC output module.

1794-IE4XOE2XT

4 Input/2 Output Analog Combo Module

11,800,802

8.47E-08

5.99E-10

1794-IE8XT

8 Input analog Module

14,041,000

7.12E-08

5.03E-10

1794-OE4XT

4 Output Analog Module

11,381,744

8.79E-08

6.22E-10

1794-IF2XOF2IXT

2 Input/2 Output Isolated Analog Combo Module

6,317,918

1.58E-07

1.13E-09

1794-IF4IXT

4 Isolated Input Analog Module

7,297,140

1.37E-07

9.75E-10

1794-IF4ICFXT

4 Isolated Input Analog Module

7,297,140

1.37E-07

9.75E-10

1794-OF4IXT

4 Isolated Output Analog Module

5,493,902

1.82E-07

1.30E-09

1794-IJ2XT

2 Ch. Frequency Counter Module

11,714,128

8.54E-08

6.04E-10

1794-IRT8XT

8 TC/RTD Input Analog Module

8,204,792

1.22E-07

8.66E-10

(1)

MTBF measured in hours.

(2)

Calculated using field-based values for components

(3)

λ

= Failure Rate = 1/MTBF

Table 1.3 FLEX I/O Product Probability of Undetected Dangerous Failure per Hour (PFH) Calculations (T

1

= 1

yr

)

Catalog Number

Description

Mean Time
Between Failure
(MTBF)

(1)

λ

(3)

Calculated PFH
1oo2 architecture

Table 1.4

Catalog Number:

Description:

MTBF:

Calculated
1oo2 PFD:

1794-ACNR15

ControlNet Dual Media
Adapter 1.5

3,259,605

1.56E-06

1794-IB16

24V DC Input Module

6,409,846

4.34E-06

1794-IB16

24V DC Input Module

6,409,846

4.34E-06

1794-OB16

24V DC Output Module

4,284,857

9.62E-06

1794-OW8

Relay Output Module

1,312,973

1.20E-06

1756-L63B

1

ControlLogix Controller

2,460,065

2.33E-04

1756-CNB

ControlNet Bridge Module

3,596,087

1.15E-04

1756-CNB

ControlNet Bridge Module

3,596,087

1.15E-04

Total PFD calculation for a safety loop consisting of these products:

3.70E-04