Publication 1794-RM001G-EN-P - December 2011

3-6 FLEX I/O Modules

Users can also wire a standard digital output module in series with an isolated
relay output module in series with a critical actuator. In the event that a failure
is detected, the output from both output modules must be set to OFF to
guarantee the Output Loads de-energize. This is shown in Figure 3.6.

Figure 3.6 ControlLogix/FLEX I/O Standard Output Module Wiring With an Isolated
Relay Module

1 2

3 4 5

6 7

8 9 10 11 12 13 14 15

0

24VDC SINK INPUT

1794-IB16

1 2

3 4 5

6 7

8 9 10 11 12 13 14 15

0

24VDC SOURCE OUTPUT

1794-OB16

1 2

3 4 5

6 7

8 9 10 11 12 13 14 15

0

24VDC SOURCE OUTPUT

1794-OB16

Isolated Relay
Output Module

43364

Standard Digital
Input Module

Standard Digital
Output Module

+24V

COM

Wire output point
to input point to
verify the correct
state of the output

Output

Output

Actuator

+24V

COM

Note 1: An external relay can be replaced with an isolated
relay module which is mounted in another FLEX I/O rail.