Troubleshoot the Adapter Chapter 6

POINTBus Status

Off

Device not powered – check module status indicator.

Flashing red/green

LED cycle power test present.

Flashing red

Recoverable fault occurred:

• At cycle power the number of expected modules does not equal the number of modules

present

• A module is missing
• Node fault (I/O connection timeout) occurred.

Solid red

Unrecoverable fault occurred – the adapter is bus off.

Flashing green

Firmware (NVS) update in progress.

Solid green

Adapter online with connections established (normal operation,
Run mode).

System Power

Off

Not active; field power is off or DC-DC converter problem present.

Solid green

System power is on; DC-DC converter is active (5V).

Field Power

Off

Not active; field power is off.

Solid green

Power is on; 24V DC is present.

Status Indicators for 1734-AENT Adapter

Indicator

Status

Description