Chapter 2 Install Your 1734 POINT I/O EtherNet/IP Adapter

Mount the POINT I/O Adapter on a DIN Rail

1. Make sure the DIN rail locking screw (orange) is in horizontal position.
2. Position the adapter vertically above an IEC standard (35 x 7.5 x 1 mm)

top-hat DIN rail at a slight angle (DIN rail: Allen-Bradley part number

199-DR1; 46277-3).

3. Press down firmly to install the adapter on the DIN rail, noting that the

locking mechanism locks the adapter to the DIN rail.

4. Set the network address thumbwheel switches to the desired value. See

Set

the Network Address

in chapter

3

for details on setting the IP address.

5. Slide the safety end cap up to remove it, exposing the backplane and power

interconnections.

ATTENTION: Allow 25.4 mm (1.0 in.) of space between adjacent
equipment for adequate ventilation.

WARNING: If you connect or disconnect the communications cable
with power applied to this module or any device on the network, an
electrical arc can occur. This could cause an explosion in hazardous
location installations.

Be sure that power is removed or the area is nonhazardous before
proceeding.

ATTENTION: Do not remove or replace an Adapter Module while power
is applied. Interruption of the backplane can result in unintentional
operation or machine motion.

1734-AENT Series B

Module
Status

Network
Activity

Network
Status

Point Bus
Status

System
Power

Field
Power

POINT I O

75.30

(2.96)

74.00

(2.91)

132.72

(5.23)

52.23

(2.06)

35.55

(1.40)

A

B

45174

A = DIN rail
B = Secure DIN rail approximately every 200 mm (7.8 in.)