Chapter 6 Troubleshoot the Adapter

Status Indicators for POINT I/O Adapters

The following describes the status indicators on the 1734-AENT.

0 2

0

43264

System Power
Field Power

Module Status
Network Activity
Network Status
POINTBus Status

Status Indicators for 1734-AENT Adapter

Indicator

Status

Description

Module Status

Off

No power applied to device

Flashing green

Device needs commissioning due to missing, incomplete, or incorrect configuration.

Solid green

Device is operating normally.

Flashing Red

Recoverable fault. Complete firmware update, verify address switches.

Solid red

Unrecoverable fault has occurred:

• Self-test failure present (checksum failure, or RAMtest failure at cycle power).
• Firmware fatal error.

Network Activity

Off

No link established.

Flashing green/Off

Transmit or receive activity present.

Steady green

Link established.

Network Status

Off

Device not initialized. The module does not have an IP address.

Flashing green

No CIP connections present. Device has an IP address, but no CIP connections are
established.

Green

CIP connections present. Device online and has an IP address, and CIP connections are
established.

Flashing red

One or more CIP connections in timed-out state. Check for I/O module failure and controller
operation.
Note: This does not apply to POINTGuard I/O connection timeout.

Solid red

Duplicate IP address detected.
Verify IP address setting and correct, as needed.

Flashing red/green

The module is performing a self-test (only occurs during cycle power test).