Using m0 and m1 files for initial configuration – Rockwell Automation 1746-QS,D17466.19 SYNCHRONIZED AXES MODULE User Manual
Page 46
Using Processor Files
C–4
Publication 1746-6.19 March 1998
Configuration parameters for M0 and M1 files can be stored in three
locations: on PC disk, in SLC-processor N files, and in module FLASH
memory. The “P” command activates the parameters (moves them
from RAM to control CPU in the module).
Configuration
Parameters
PC
Configuration
Parameters
SLC
Configuration
Parameters
QS
Module
M0/M1 Files
in Module
RAM
Module’s
Control
CPU
P Cmd.
COPY
Disk
N Files
FLASH
Power-up
P Cmd.
M0 and M1 Memory Map for Ladder Logic
M0 and M1 files both have the same 16-word memory map. They are
addressed in ladder logic as M0e:n or M1e:n (e = rack #, n = word #).
Copy these
parameters:
To/From these file addresses:
Copy these
parameters:
Axis 1
Axis 2
Axis 3
Axis 4
Configuration
e.0
e.16
e.32
e.48
Scale
e.1
e.17
e.33
e.49
Offset
e.2
e.18
e.34
e.50
Extend Limit
e.3
e.19
e.35
e.51
Retract Limit
e.4
e.20
e.36
e.52
Proportional Gain
e.5
e.21
e.37
e.53
Integral Gain
e.6
e.22
e.38
e.54
Differential Gain
e.7
e.23
e.39
e.55
Extend Feedforward
e.8
e.24
e.40
e.56
Retract Feedforward
e.9
e.25
e.41
e.57
Extend Accel Feedforward
e.10
e.26
e.42
e.58
Retract Accel Feedforward
e.11
e.27
e.43
e.59
Dead Band Eliminator
e.12
e.28
e.44
e.60
In Position
e.13
e.29
e.45
e.61
Following Error
e.14
e.30
e.46
e.62
Auto Stop
e.15
e.31
e.47
e.63
Using M0 and M1 Files
for Initial Configuration