Rockwell Automation 1771-TCM,D17716.5.108 TEMPERATURE CONTROL MOD User Manual
Page 62

Monitoring Status Data
Chapter 7
7-12
Word Description
Bits
17
0
LoopĆ6 Enable
•
0 = Loop 6 disabled.
•
1 = Loop 6 enabled.
1
LoopĆ6 Auto/Manual Mode Select Ċ (controlled by bit 1 of word 22 of the dynamic block)
•
0 = Loop 6 is in the manual mode Ċ the manual output value (from word 25, dynamic block) is used as the CV value.
•
1 = Loop 6 is in the automatic mode Ċ the PID algorithm generates the CV value.
2
LoopĆ6 Open Circuit
•
0 = LoopĆ6 thermocouple circuit is closed (connection OK).
•
1 = .LoopĆ6 thermocouple circuit is open (connection broken).
3
LoopĆ6 Parameters valid
•
0 = Power has been interrupted since valid parameters for loop 6 have been blockĆtransferred.
•
1 = Valid parameters for loop 6 have been blockĆtransferred since last loss of power .
4
LoopĆ6 Calibration Fault
•
0 = LoopĆ1 calibration is OK.
•
1 = LoopĆ1 cannot operate with as calibrated.
5
LoopĆ6 SetĆPoint Select Ċ (controlled by bit 2 of word 22 of the dynamic block)
•
0 = Select the standbyĆtemperature setĆpoint value from word 23 of the dynamic block.
•
1 = Select the runĆtemperature setĆpoint value from word 24 of the dynamic block.
6
LoopĆ6 Parameter Value Error
•
0 = LoopĆ6 parameter values OK.
•
1 = LoopĆ6 parameter value error.
7
LoopĆ6 AutoĆTuning Complete
•
0 = LoopĆ6 autoĆtuning is not complete.
•
1 = LoopĆ6 autoĆtuning is complete.
8
Reserved.
9
Reserved.
10
LoopĆ6 Thermal Runaway Ċ (set in words 22 and 23 of the configuration block)
•
0 = LoopĆ6 is operating within thermal runaway limit..
•
1 = LoopĆ6 has exceeded the thermal runaway limit. and the CV value has been forced..
11
LoopĆ6 High CV Limit Ċ (set in word 7 of the configuration block)
•
0 = LoopĆ6 CV value is below the high CV limit.
•
1 = LoopĆ6 CV value is at the high CV limit.
12
LoopĆ6 Low CV Limit Ċ (set in word 8 of the configuration block)
•
0 = LoopĆ6 CV value is above the low CV limit.
•
1 = LoopĆ6 CV value is at the low CV limit.