Monitoring Status Data
Chapter 7
7-6
Word Description
Bits
8
0
LoopĆ3 Enable
•
0 = Loop 3 disabled.
•
1 = Loop 3 enabled.
1
LoopĆ3 Auto/Manual Mode Select Ċ (controlled by bit 1 of word 1
0
of the dynamic block)
•
0 = Loop 3 is in the manual mode Ċ the manual output value (from word 13, dynamic block) is used as the CV value.
•
1 = Loop 3 is in the automatic mode Ċ the PID algorithm generates the CV value.
2
LoopĆ3 Open Circuit
•
0 = LoopĆ3 thermocouple circuit is closed (connection OK).
•
1 = .LoopĆ3 thermocouple circuit is open (connection broken).
3
LoopĆ3 Parameters valid
•
0 = Power has been interrupted since valid parameters for loop 3 have been blockĆtransferred.
•
1 = Valid parameters for loop 3 have been blockĆtransferred since last loss of power .
4
LoopĆ3 Calibration Fault
•
0 = LoopĆ3 calibration is OK.
•
1 = LoopĆ3 cannot operate with as calibrated.
5
LoopĆ3 SetĆPoint Select Ċ (controlled by bit 2 of word 10 of the dynamic block)
•
0 = Select the standbyĆtemperature setĆpoint value from word 11 of the dynamic block.
•
1 = Select the runĆtemperature setĆpoint value from word 12 of the dynamic block.
6
LoopĆ3 Parameter Value Error
•
0 = LoopĆ3 parameter values OK.
•
1 = LoopĆ3 parameter value error.
7
LoopĆ3 AutoĆTuning Complete
•
0 = LoopĆ3 autoĆtuning is not complete.
•
1 = LoopĆ3 autoĆtuning is complete.
8
Reserved.
9
Reserved.
10
LoopĆ3 Thermal Runaway Ċ (set in words 22 and 23 of the configuration block)
•
0 = LoopĆ3 is operating within thermal runaway limit..
•
1 = LoopĆ3 has exceeded the thermal runaway limit. and the CV value has been forced..
11
LoopĆ3 High CV Limit Ċ (set in word 7 of the configuration block)
•
0 = LoopĆ3 CV value is below the high CV limit.
•
1 = LoopĆ3 CV value is at the high CV limit.
12
LoopĆ3 Low CV Limit Ċ (set in word 8 of the configuration block)
•
0 = LoopĆ3 CV value is above the low CV limit.
•
1 = LoopĆ3 CV value is at the low CV limit.