Rockwell Automation 1771-TCM,D17716.5.108 TEMPERATURE CONTROL MOD User Manual
Page 58

Monitoring Status Data
Chapter 7
7-8
Word Description
Bits
11
0
LoopĆ4 Enable
•
0 = Loop 4 disabled.
•
1 = Loop 4 enabled.
1
LoopĆ4 Auto/Manual Mode Select Ċ (controlled by bit 1 of word 14 of the dynamic block)
•
0 = Loop 4 is in the manual mode Ċ the manual output value (from word 17, dynamic block) is used as the CV value.
•
1 = Loop 4 is in the automatic mode Ċ the PID algorithm generates the CV value.
2
LoopĆ4 Open Circuit
•
0 = LoopĆ4 thermocouple circuit is closed (connection OK).
•
1 = .LoopĆ4 thermocouple circuit is open (connection broken).
3
LoopĆ4 Parameters valid
•
0 = Power has been interrupted since valid parameters for loop 4 have been blockĆtransferred.
•
1 = Valid parameters for loop 4 have been blockĆtransferred since last loss of power .
4
LoopĆ4 Calibration Fault
•
0 = LoopĆ4 calibration is OK.
•
1 = LoopĆ4 cannot operate with as calibrated.
5
LoopĆ4 SetĆPoint Select Ċ (controlled by bit 2 of word 14 of the dynamic block)
•
0 = Select the standbyĆtemperature setĆpoint value from word 15 of the dynamic block.
•
1 = Select the runĆtemperature setĆpoint value from word 16 of the dynamic block.
6
LoopĆ4 Parameter Value Error
•
0 = LoopĆ4 parameter values OK.
•
1 = LoopĆ4 parameter value error.
7
LoopĆ4 AutoĆTuning Complete
•
0 = LoopĆ4 autoĆtuning is not complete.
•
1 = LoopĆ4 autoĆtuning is complete.
8
Reserved.
9
Reserved.
10
LoopĆ4 Thermal Runaway Ċ (set in words 22 and 23 of the configuration block)
•
0 = LoopĆ4 is operating within thermal runaway limit..
•
1 = LoopĆ4 has exceeded the thermal runaway limit. and the CV value has been forced..
11
LoopĆ4 High CV Limit Ċ (set in word 7 of the configuration block)
•
0 = LoopĆ4 CV value is below the high CV limit.
•
1 = LoopĆ4 CV value is at the high CV limit.
12
LoopĆ4 Low CV Limit Ċ (set in word 8 of the configuration block)
•
0 = LoopĆ4 CV value is above the low CV limit.
•
1 = LoopĆ4 CV value is at the low CV limit.